登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给水排水工程 > 正文

11 扬州某开发区设备大楼给排水设计毕业论文

 2022-04-11 08:04  

论文总字数:35903字

摘 要

给水系统分区供水,从市政管网上接一根DN200的引入管,负一层至地上四层为市政管网直供;五至十六层为加压区,采用变频泵加压供水。建筑室内排水采用污、废水分流制,室外排水采用污废合流制,排入检查井后,再排入市政污水管网。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑雨水采用外排水,选择重力半有压流系统,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为二类高层建筑,室外消火栓用水量30L/s,室内消火栓用水量40L/s,火灾延续时间2h。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。消防水池采用钢筋混凝土结构,置于地下室泵房外侧,有效容积641立方。

该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量30L/s。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分5个区。选用箱泵一体化消防增压稳压设备(包含18立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给水系统 排水系统 消火栓系统 自动喷水灭火系统 雨水系统

Water Supply and Drainage Design of an Agency Office in Changzhou

Abstract

Water supply system of regional water supply, from the municipal pipe online access a root DN200 into pipe, negative a layer to layer for the municipal pipe network direct supply; 5 to 16 layer for pressor area, the variable frequency pump pressurized water supply. Building interior drainage with sewage, waste water diversion system, outdoor drainage using sewage streaming of scrap, discharged into the inspection wells, and then discharged into the municipal sewage pipe network. Basement drainage through a drainage ditch pooled row to sump, the submersible sewage pump upgrade row to check well. Construction of rainwater by external drainage, gravity half pressure flow system, rain after collecting roof rain water bucket by the rain water pipe row to inspection wells.

According to the specification, the building is the second class of high-rise buildings, outdoor fire hydrant water is, indoor fire hydrant water 40L / s fire continue 2H hydrant enrich the water column height of 12M, hose length of 25m, the water gun nozzle flow 5.16L/s, fire vertical pipe diameter was DN100. in the roof layer test fire a, each indoor fire hydrant boxes are equipped with remote start the fire pump button. Fire pool by the reinforced concrete structure, arranged on the outer sides of the basement pump room, the effective volume 641 cubic.

The building adopts wet type automatic water spraying fire extinguishing system, sprinkler system design flow 30L/s. alarm valve is arranged on the basement pump room, each layer shall be provided with flow indicator, the end water test equipment and signal valve, the signal was sent to fire control center. The project of automatic water spraying arc ignition system divided into five zones. Selection of tank pump integration of fire pressure stabilizing device (including 18 cubic meters of fire water tank) storage fire initial 10min of automatic water spraying fire extinguishing system, indoor fire hydrant system water, the initial fire by water supply, post fire from the basement of the fire pump and spray pump water supply.

Keyword: water-supply system drainage system hydrant system automatic sprinkler system rainwater system

扬州某开发区商务大楼给排水设计书

一、工程概况

该课题为扬州某开发区商务大楼给排水设计,该建筑属高层公共建筑,建筑已完成条件图设计,现要求给排水专业对其进行给排水设计。该建筑共十六层,建筑总高度为55.5m,地上十六层,地下一层。地下层设生活水池、消防水池、水泵房,并有自动报警装置。因为该建筑为公共建筑,所以除设有消水栓系统外,还设有自动喷水灭火系统。该建筑外墙的背面、正面30M处分别有一市政给水管道经过,管顶标高为-1.5M,管径为DN200,供水最低压力为25M水头;建筑背面50M、60M处分别有一市政污水管、市政雨水管,管底标高分别为-2.0M和-3.0M。

二、设计依据

1.建筑给水排水设计规范GBJ50015-2003(2009年版);

2.建筑设计防火规范GB50016-2006(2006年版);

3.高层民用建筑设计防火规范GB50045-95(2005版);

4.给排水制图标准GB/T50106-2001

5.自动喷水灭火系统设计规范GB50084-2001(2005版);

6.有关文件及各工程提供的资料,包括16张建筑图纸。

三、设计内容

本设计应包括生活给水系统、消防系统(包括消火栓系统和自动喷水灭火系统)、生活排水系统、雨水系统。

四、完成的工作量

1.设计计算说明书一本,包括如下内容:

(1)方案的选择和比较;

(2)给水系统水力计算;

(3)排水系统水力计算;

(4)消火栓系统水力计算;

(5)自动喷水灭火系统水力计算;

(6)主要设备的选型与计算;

(7)格式:封面,目录,英文摘要,中文摘要,正文,参考文献。

2.图纸

请支付后下载全文,论文总字数:35903字

您需要先支付 80元 才能查看全部内容!立即支付

企业微信

Copyright © 2010-2022 毕业论文网 站点地图