登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给水排水工程 > 正文

13 淮安新世纪商城给排水设计毕业论文

 2022-04-11 08:04  

论文总字数:29265字

摘 要

给水系统分区供水,从市政管网上接一根DN50的引入管,负一层至地上三层为市政管网直供;四至十层为加压区,采用变频泵加压供水。建筑室内排水采用污、废水合流制,排入检查井后,再排入市政污水管网。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑雨水采用外排水,选择重力半有压流系统,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为二类高层建筑,室外消火栓用水量30L/s,室内消火栓用水量20L/s,火灾延续时间3h。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。消防水池采用钢筋混凝土结构,置于地下室泵房外侧,有效容积648立方。

该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量30L/s。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分12个区。选用箱泵一体化消防增压稳压设备(包含18立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给水系统 排水系统 消火栓系统 自动喷水灭火系统 雨水系统

Water Supply and Drainage Design of New Century mall in Huaian

Abstract

Water supply system partition from the municipal pipe connected to the Internet introduced a DN50 pipe, the negative layer to the ground three municipal direct supply pipe network; fourth ten layers pressurized zone, variable frequency pump pressurized water supply. Architecture Indoor use sewage drainage, wastewater Combined, after checking into the wells, and then discharged into municipal sewage pipe network. Basement drainage by drains discharge to a collection sump, the submersible sewage pump check up and drained well. Outside the building using rainwater drainage, choose semi-pressurized gravity flow system, rain water bucket after roof rainwater collection pipe to discharge from the manholes.

According to the specification, the building of two types of high-rise buildings, outdoor fire hydrant water 30L / s, fire hydrant water 20L / s, fire duration 3h. Hydrant enrich the water column height of 12m, hose length 25m, gun nozzle flow 5.16L / s, fire standpipe diameter is DN100. In the attic is provided a test fire hydrant, fire hydrant box each have a remote start the fire pump buttons. Fire water reinforced concrete structure, located on the outside basement pump room, the effective volume of 648 cubic meters.

The building wet automatic sprinkler system, sprinkler system design flow 30L / s. Alarm valve is provided in the basement pump room, the layers are set flow indicator, end water apparatus and a signal valve, which signals are sent to the fire control center for processing. Automatic sprinkler system of the project in 12 districts. Selection box integrated fire booster pump regulator device (containing 18 m3 fire water tank) storing the initial 10min fire sprinkler systems, fire hydrant system, water, initial fire extinguishing water from the tank, the latter by the fire in the basement of the fire pump and spray shower pump water.

Keyword: water-supply system drainage system hydrant system automatic sprinkler system rainwater system

淮安新世纪商场给排水设计任务书

一、工程概况

该建筑共十层,建筑总高度为45.6m,地上十层,地下二层。地下层设生活水池、消防水池、水泵房,并有自动报警装置。因为该建筑为公共建筑,所以除设有消水栓系统外,还设有自动喷水灭火系统。该建筑外墙的背面、正面30m处分别有一市政给水管道经过,管顶标高为-1.5m,管径为DN200,供水最低压力为20m水头;建筑背面50m、60m处分别有一市政污水管、市政雨水管,管底标高分别为-2.0m和-3.0m。

二、设计依据

1.建筑给水排水设计规范GBJ50015-2003(2009年版);

2.建筑设计防火规范GB50016-2006(2006年版);

3.高层民用建筑设计防火规范GB50045-95(2005版);

4.给排水制图标准GB/T50106-2001

5.自动喷水灭火系统设计规范GB50084-2001(2005版);

6.有关文件及各工程提供的资料,包括16张建筑图纸。

三、设计内容

本设计应包括生活给水系统、消防系统(包括消火栓系统和自动喷水灭火系统)、生活排水系统、雨水系统。

四、完成的工作量

1.设计计算说明书一本,包括如下内容:

(1)方案的选择和比较;

(2)给水系统水力计算;

(3)排水系统水力计算;

(4)消火栓系统水力计算;

(5)自动喷水灭火系统水力计算;

(6)主要设备的选型与计算;

(7)格式:封面,目录,英文摘要,中文摘要,正文,参考文献。

2.图纸

请支付后下载全文,论文总字数:29265字

您需要先支付 80元 才能查看全部内容!立即支付

企业微信

Copyright © 2010-2022 毕业论文网 站点地图