登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给排水科学与工程 > 正文

某高层住宅楼给排水设计毕业论文

 2022-03-10 08:03  

论文总字数:28795字

摘 要

本设计为十七层的建筑给排水设计,一二层为商铺,三至十七层为住宅,主要包括给水系统,排水系统,消防系统。给水系统采用分区供水,一层至五层为低区,由市政管网直供,六至十二层为中区,十三至十七层为高区,采用变频调速加压供水设备供水。生活排水采用污、废水分流制,废水直接排放至市政排水管,污水经化粪池处理后排放至指正排水管。屋面雨水排放选外排水排放方式,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为中度危险I级。室内消防流量40L/s,室外30L/s。充实水柱取11m,水龙带长度取20m,消防立管管径为DN100。在顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

该建筑采用湿式自动喷淋灭火系统,报警阀设于室外地下泵房,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。屋顶水箱为18立方米为消防水箱,贮存10min自动喷水灭火系统、室内消火栓系统用水量。自动喷水灭火系统和消火栓系统的初期灭火由水箱供水,后期供水由地下室的消防水泵和自喷泵供水。

关键词:给水系统 排水系统 消火栓系统 自动喷水灭火系统 雨水系统

Summary of water supply and drainage design of high-rise residential building

This design is 17 - floor building water supply and drainage design, one - two - tier shop, three to 17 floors for residential, mainly including water supply system, drainage system, fire control system. The water supply system uses the zoned water supply, one to five layers as the low area, the municipal pipe network directly, six to twelve layers are central, 13 to 17 layers are high area, and the frequency conversion speed regulation pressure water supply equipment water supply. The domestic drainage shall be made of sewage and waste water, and the waste water shall be discharged directly to the municipal drainage pipe, and the sewage shall be discharged to the correction drain pipe after the treatment of the septic tank. The roof rainwater drainage shall be drained by the drainage system, and the rainwater shall be drained by the rainwater pipe after the roof rainwater bucket is collected.

According to the specification, the building is a moderate hazard class I. Indoor fire flow 40l / s, outdoor 30l / s. Enrich the water column to take 11m, the hose length shall be 20m, and the pipe diameter of fire control pipe shall be dn. A fire hydrant is set up at the top level, and a button is provided inside each indoor fire hydrant box to start a fire pump remotely.

The building adopts a wet automatic sprinkler system, alarm valve is arranged in the outdoor underground pump house, and water flow indicator, end water test device and signal valve are set in each layer, and the signal is sent to the fire control center for processing. The roof water tank is 18 cubic meters as the fire water tank, and the water consumption of automatic sprinkler system and indoor hydrant system shall be stored for 10 minutes. The initial fire extinguishing system of automatic sprinkler system and fire hydrant system is supplied by water tank, and the later water supply is supplied by the fire pump and self - spraying pump in the basement. 
Key words: water supply system, drainage system, fire hydrant system, automatic sprinkler system, rain water system

目录

摘要

Abstract

第一章 给排水工程设计任务书 1

1.1工程概况 1

1.2 设计依据 1

1.3设计内容 1

1.4完成的工作量 1

1.5设计进度计划 2

第二章 设计说明书 2

2.1给水系统 2

2.1.1 给水水源 2

2.1.2 给水系统的选择 3

2.1.3方案选择依据 3

2.1.4给水系统的组成 4

2.1.5给水管道布置与敷设 4

2.2排水系统 4

2.2.1排水系统的选择 4

2.2.2排水系统的组成 5

2.2.3排水管道安装要求 5

2.3雨水排水系统 6

2.3.1雨水排水系统的选择 6

2.3.2雨水排水系统的组成 6

2.3.3雨水管道的敷设与布置 6

2.4室内消火栓系统 6

2.4.1室内消火栓系统的选择 6

2.4.3消火栓的安装 7

2.5自动喷淋系统 7

2.5.1自动喷水灭火系统的选择 7

2.5.2自动喷水灭火系统的组成 8

2.5.3喷头的选择与布置 8

2.5.4喷淋系统的安装 8

第三章 设计计算书 9

3.1给水系统的计算 9

3.1.1生活用水量计算 9

3.1.2商铺设计秒流量的确定 10

3.1.3住宅设计秒流量 11

3.1.5高区变频泵选择 16

3.1.6中区变频泵选择 17

3.1.7低区给水系统所需压力校核 17

3.2 室内排水系统的计算 17

3.2.1排水系统要求 17

3.2.2排水水力计算 18

3.2.3废水管水力计算 22

3.2.4化粪池的计算 23

3.3雨水排水系统的计算 25

3.3.1暴雨强度 25

3.3.2汇水面积计算 26

3.4室内消火栓给水系统的计算 29

3.4.1消防水箱的设置 29

3.4.2消防水池的设置 30

3.4.3消火栓布置 31

3.4.4消火栓的水力计算 31

3.4.5水泵接合器选定 33

3.4.6消火栓减压计算 34

3.4.7消防水泵选择 34

3.4.7高位水箱设置高度 35

3.4.8室外消火栓的设置 36

3.5自动喷淋灭火系统的计算 37

3.5.1自动喷淋灭火系统的基本数据 37

3.5.2自动喷淋灭火系统水力计算 37

3.5.3加压设备选择 41

3.5.4水泵接合器选择 41

参考文献 43

结束语 44

致 谢 45

请支付后下载全文,论文总字数:28795字

您需要先支付 80元 才能查看全部内容!立即支付

企业微信

Copyright © 2010-2022 毕业论文网 站点地图