登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给排水科学与工程 > 正文

某住宅楼建筑给排水设计毕业论文

 2020-05-24 12:05  

摘 要

本设计一层至地上四层为市政管网直供,五至十九层为变频泵供水的给水方式。直供部分从市政给水管网接一根DN150的引入管,分出两根DN100的给水管接至地下一层生活水箱和消防水池。消防水池采用砖砌混凝土结构,置于地下室。排水采用生活污、废水合流制。泵房排水槽经汇集排至地下一层污水井,经潜污泵提升排至检查井再排入市政排水管。建筑二层及以上的生活污水管在一层吊顶内,将各单元生活污水管适当转换到排水立管后排出室外。屋面雨水排放选择重力式雨水系统,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为一类建筑,属中度危险一级。室内消防流量40L/s,室外30L/s。充实水柱取12m,水龙带长度取25m,水枪喷嘴流量5.2L/s,消防立管管径为DN100、DN150。在顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

该建筑采用湿式自动喷淋灭火系统,报警阀设于地下一层,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分1个区。屋顶水箱为36立方米为消防水箱,贮存10min自动喷水灭火系统、室内消火栓系统用水量。自动喷水灭火系统和消火栓系统的初期灭火由水箱供水,后期供水由地下室的消防水泵和自喷泵供水。

关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统

Abstract

In this design,on the 1F to the 4F for municipal services tube the net keep provide,5 to 19 F is frequency conversion water supply pump as the water supply way. Keep provide part the net connect lead of a DN150 into the tube from the municipal services water pipe,another two lead of DN100 into tube connect to -1 F life pond and fire fight pond. Life pond and fire fight pond adoption the brick carve concrete structure and placed in the basement. Drainage using domestic sewage and waste water combined system. Except the drainage system of 1F to 3F use stack vent, the other are used specific vent stack. The pump house drain slot through gather together row to the -1 F sewage well,through submersible sewage pumps promote row to check well again through septic tank processing rear row go into municipal services drain pipe. Building 2 F above of life the soil pipe is in the 1 F hang the crest,each unit life soil pipe appropriate gather together conversion to arrive drain to sign tube rear row outdoors. Select gravity roof rainwater drainage system. House noodles rain water through the house noodles rain roof drain after collection from rain water tube the row go to the check well.

According to the codes,the building is class one fireproof construction,belongs to one class of medium degree dangerous. Indoor fire fight discharge is 30 L/s and outdoor is 30 L/s,full water spout is 12m,hoses is 25 m,water gun spray the mouth discharge is 5.2 L/s,and the fire standpipe diameter is DN100,DN150. In the top set a fire hydrant as an experiment hydrant. All hydrant cabinet set a long-distance leave start fire fight pump of button.

The building is arranged with wet pipe fire sprinkler system. Alarm valve is arranged on the basement. Each floor should set a flow indicator,End water-test equipment and signal valve,its signal all send into fire fight control center to carry on processing. The automatic sprinkler system is divided into one zones. The fire tank is 36 cubic meters,have 10min fire water storage. Automatic sprinkler system and hydrant system of initial stage extinguish fire from the water tank supply water. Latter water supply is supply by fire pump and spray pump in the basement.

Keyword: Water-supply system、Drainage system、Hydrant system、Automatic sprinkler system、Rainwater system

目 录

某高层住宅楼建筑给排水设计 1

摘 要 1

Abstract 2

第一章 给排水工程设计任务书 4

1.1 工程概况 4

1.2设计依据 4

1.3 设计内容 4

1.4设计图纸及要求 4

1.4.1撰写开题报告(综述) 4

1.4.2设计说明书 4

1.4.3图纸内容 5

1.4.4设计进度计划 5

第二章 设计说明书 6

2.1给水系统 6

2.2排水系统 7

2.3消火栓给水系统 8

2.4自动喷淋系统 8

第三章 计算说明书 9

3.1给水系统 9

3.1.1室内给水系统计算 9

3.1.2生活水箱容积 10

3.1.3室内管网压力 10

3.2排水系统 17

3.2.1室内排水系统计算 18

卫生器具排水定额及排水管道设计秒流量公式的确定 18

3.2.2建筑内排水管道计算 18

3.2.3地下室排水系统计算 28

4、首层汽车库排水系统计算 29

5、消防电梯排水系统计算 29

3.3消火栓系统 29

3.3.1室内消火栓系统计算 29

3.3.2减压孔板计算 34

3.3.3水泵接合器设置 36

3.3.4消防水箱 36

3.3.5消防贮水池 36

3.4自动喷水灭火系统 37

3.4.1自动喷水灭火给水系统计算 37

3.4.2喷淋系统屋顶增压设施设计 42

3.4.3减压孔板计算 42

3.5雨水排水系统 43

3.5.1 降雨强度的确定 43

3.5.2 雨水立管的布置 43

3.5.3 雨水水力计算 45

参考文献 46

结束语 47

谢辞 48

第一章 给排水工程设计任务书

1.1 工程概况

某高层住宅楼地下一层为车库,地上一层为商场,建筑高度59.00m,群楼一层,建筑高度5.30m。市政管网可以提供的常年资用水头均为0.25Mpa。城市排水管网为污、雨分流制排放系统。

1.2设计依据

(1)《建筑给水排水设计规范》GB50015-2003(2009年版)

(2)《室外给水设计规范》GB50013-2006(2006年版)

(3)《室外排水设计规范》GB50014-2006(2011年版)

相关图片展示:

您需要先支付 80元 才能查看全部内容!立即支付

企业微信

Copyright © 2010-2022 毕业论文网 站点地图